Skip to main content

FDS Validation (NUREG 1934)

FDS Validation (NUREG 1934)

FRI3D generates complete FDS input decks directly from the 3D plant model — compartment boundaries, obstructions, mechanical ventilation, leakage, fire sources, and measurement devices. To validate this generation pipeline end-to-end, FRI3D's output is benchmarked against the U.S. NRC NUREG-1934 (EPRI 1023259), Appendix A — Main Control Room (MCR) reference scenario, one of the standard fire-model V&V cases used by the NRC and EPRI.

Reference case

The MCR case models a control-cabinet fire in a nominally sealed 24.6 m × 16.2 m × 5.2 m control room:

  • Fire: electrical cabinet fire, t² growth to a 702 kW peak at 720 s (NUREG/CR-6850 cabinet fire profile), XPE/Neoprene fuel chemistry with a CO yield of 0.1.
  • Ventilation: two supply registers and six exhaust registers. Two scenarios are run — smoke purge (ventilation switched to 5× flow, ≈ 25 ACH, at t = 10 s) and no purge (ventilation off).
  • Leakage: a single 0.0117 m² leakage path to ambient (door crack).
  • Simulation: FDS 6, 1200 s.

Methodology

The published NRC FDS input decks are run unmodified as the baseline. The FRI3D model of the same room is then built in the FRI3D UI (compartment geometry with boundary walls, cabinets, mechanical vents, leakage, and the NUREG fire ramp), and the FDS deck is generated entirely by FRI3D — the only hand edit is the per-scenario fan state (purge ramp multiplier / fans off), which mirrors how the NRC decks encode the two scenarios. Both decks are executed with the same FDS build (6.7.9) on the same machine and compared on the quantities both decks emit:

QuantityFRI3D deck outputNRC deck output
Heat release rateHRRHRR
Hot gas layer temperatureMCR_HGL_TEMPVAL_HGL_TEMP
Hot gas layer heightMCR_HGL_HEIGHTVAL_HGL_HEIGHT

A structural note: in the NRC deck the mesh boundary is the room, while FRI3D places the room (wall obstructions generated from the compartment boundary lattice) inside a larger domain. FDS's automatic pressure-zone detection finds the FRI3D room to be a fully isolated volume — a meaningful validation result in itself: the wall lattice FRI3D generates is airtight on the FDS grid (no unintended gaps at wall joints or corners). Wall and ceiling materials generated by FRI3D (16 mm gypsum board, 0.5 m concrete) match the NRC deck exactly.

Results (smoke-purge scenario)

Matched-time comparison over the full 1200 s run (FRI3D-generated deck vs NRC FDS 6.7.9 baseline):

t (s)HRR (kW) FRI3D / NRCHGL temp (°C) FRI3D / NRCHGL height (m) FRI3D / NRC
12017.3 / 17.320.0 / 20.95.20 / 5.05
24073.4 / 73.323.9 / 25.24.03 / 4.44
360168.4 / 168.326.4 / 27.63.36 / 3.60
480302.5 / 302.631.0 / 33.73.33 / 3.30
600474.9 / 473.933.9 / 42.12.55 / 3.07
720686.0 / 688.439.7 / 51.52.68 / 2.84
840701.1 / 702.142.4 / 57.32.68 / 2.61
960702.7 / 699.742.8 / 60.12.62 / 2.49
1080701.7 / 700.143.4 / 62.72.64 / 2.48
1200700.8 / 701.743.9 / 63.52.72 / 2.40

FRI3D generated deck vs NRC FDS6 baseline — smoke purge

Heat release rate — exact agreement over the entire run: the growth ramp, the 702 kW peak, and the full sustained-burn plateau. The FDS-computed HRR (the volume-integrated heat release from the combustion model, not an echo of the input curve) matches to output precision, confirming that the fire ramp, burner area, fuel chemistry, and species yields generated by FRI3D reproduce the NRC specification, and that the FRI3D compartment, ventilation, and leakage setup sustains the same combustion (neither run is oxygen-limited).

Hot gas layer height — agreement within ~0.3 m throughout, converging as the fire matures: on the plateau the two models place the smoke layer within ~0.1–0.3 m of each other (2.72 vs 2.40 m at t = 1200 s).

Hot gas layer temperature — tracks within ~1–3 °C while the fire is small, with the FRI3D run reading progressively cooler as the fire grows and saturating at ~19 °C below the NRC value once both models plateau (43.9 vs 63.5 °C at t = 1200 s). This is a known thermal-boundary sensitivity, not a deck-generation error: the NRC deck models cabinets as hollow 1.5 mm exposed-steel shells that heat quickly and re-radiate into the hot layer, while the FRI3D model uses solid cabinet obstructions with a default insulating material that absorbs and holds that heat. Assigning the steel cabinet material in the FRI3D model closes this gap; a follow-up run with that assignment is planned.

Status

  • Smoke purge: complete to t = 1200 s (full comparison above).
  • No purge: running on the same campaign; results will be added when complete.

Reference

  • NUREG-1934 / EPRI 1023259, Nuclear Power Plant Fire Modeling Analysis Guidelines, Appendix A: Main Control Room.

Reach out

If you need help after reading this doc, email us [email protected] for an answer. .